Contents:
Procedures of Two Way Slab Design by Direct Design Method
- Determine slab type and layout
- Choose slab thickness that should be adequate for avoiding excessive deflections and satisfy shear at the interior and exterior columns.
- Choose design method (direct design method in this case)
- Calculate positive and negative moments in the slab
- Distribute moments across slab width
- Specify portion of moments to the beams, if beams are present
- Compute reinforcements for moments that found in two previous points
- Check shear strength
Limitations of Direct Design Method
- There must be at least three continuous spans in each direction. If there are fewer panels, the interior negative moments tend to be too small.
- Panels should be rectangular and the ratio of longer/ shorter spans within the panel must not exceed 2 otherwise one-way actions will prevail.
- In each direction, successive span lengths must not differ by more than one-third of the largest span length.
- Column offset of more than 10% of the span (in the direction of offset) from either axis between the centerline of the successive column is not permitted.
- This method is applicable for slabs that subjected to gravity load only.
- Unfactored service live load should not be more than two times unfactored dead load.
- f beams were used, beam relative stiffness between two perpendicular directions must be between 0.2-0.5.
Two Way Slab Design by Direct Design Method
Before the start of the two-way slab design, slab depth should be determined in addition to specifying column strips and middle strips. In this article, it is assumed that slab thickness is determined but the calculation of column and middle strips is explained in the following section:Column and middle strips
There are continuous variations of moments across slab panels therefore to help placement of steel, design moments are averaged over column strips and middle strips. The column strips are located over columns and have a width on each side of the column centerline equal to a smaller panel dimension divided by four and middle strips are located between two column strips. Figure-1 and Figure-2 illustrate the middle strip and column strip for long and short directions of the panel.Figure-1: Column and Middle Strip in Short Direction of the Panel
Figure-2: Column and Middle Strips in Long Direction of the Panel
Total static moment for a span (Mo):
Clear span (ln) which is extended from face to face of walls or columns, in the direction of moments is used to compute total static moment in a panel. A factored moment in as span is calculated as per the following equation:Figure-3: Column and middle strip in both direction of the slab with necessary parameters for calculating total static moment
Distribution of total static moment to positive and negative moments
1. For interior spans:
Total static moments are distributed to positive and negative moments as per the following ratios: Negative factored moment -Mu = 0.65Mo Positive factored moment +Mu = 0.35Mo2. For edge spans:
The total static moment is distributed to negative exterior moment, interior moment, and negative interior moment as per Table-1.Table-1: Factors applied to static moment for positive and negative moments
Figure-4: Distribution of total static moment to critical sections in interior and end spans
Lateral distribution of moments between column and middle strips
After assigning total static moments into positive and negative moments, it is necessary to distribute these moments to middle and column strips. For design purposes, moments are assumed to be uniformly distributed to column and middle strips except beams are present. Positive and negative moment distribution to column and middle strips is depended number of parameters which will be explained in the following sections: A. The ratio of (l2/l1), B. Relative stiffness (af) of beams and slabs spanning in each direction: is expressed as:Figure-5: Portion of slabs to be included for the moment of inertia calculation, edge beam (left side) & internal beam (right side)
Figure-6: Dimensions of internal and external slab for a moment of inertia calculations
C. Degree of tensional stiffness provided by edge beams which is expressed by parameterFigure-7: Two possible subdivisions of L-section in rectangles for torsion constant C
With these parameters defined positive and negative moments are assigned to a column and middle strips. Table-2 used to specify the portion of positive and negative moments to column strip and interpolations when it is required. When beam is present along column line in the direction of l1, 85% of column strip moment is resisted by the beam ifTable-2: Column strip moment, percent of a total moment at the critical section